mm(W*H*D) | 400×500×400 | 500×600×500 | 500×750×600 | 600×850×800 | 1000×1000×800 | 1000×1000×1000 |
mm(W*H*D) | 600×1650×1200 | 700×1760×1545 | 700×1910×1625 | 800×2010×1845 | 1200×2035×1850 | 1200×2035×2050 |
temperature range
A:-20~+150℃ B:-40~+150℃ C:-70~+150℃
Humidity range
20%~98%RH
Temperature deviation
±2℃
Temperature uniformity
±2℃
Temperature fluctuation
±0.5℃
heating rate
About 3 ℃/min (non-linear, no load)
cooling rate
Average 1.0 ℃/min (non-linear, no load)
Humidity deviation
±3.0%RH(>75%RH); ±5.0%RH(≤75%RH)
Humidity uniformity
± 3.0% RH (unloaded)
Humidity fluctuation
± 2.5% RH (unloaded)
Inner box material
SUS304 stainless steel plate
Outer box material
A3 cold-rolled steel plate electrostatic double-sided spray coating/SUS304 stainless steel
Insulation material
Rigid polyurethane foam
Cooling method
Air cooled (using French Taikang fully enclosed compressor)
cryogen
R404a、R23
Temperature and humidity sensor
A-grade PT100 platinum resistor
heater
Nickel chromium alloy electric heating heater
Humidifier
External humidification is adopted, and the humidification tube adopts a U-shaped design with an additional high-temperature probe hole,
Power Supply
220V±10%V/ 380V±10%V; 50Hz;
protection system
Power phase loss and phase sequence error protection, automatic water shortage alarm protection, leakage protection, heater over temperature protection, heater short circuit and other overcurrent protection
Installation environment
Temperature: 2 ℃~30 ℃; Relative humidity: ≤ 85%; Air pressure: 86kPA~106kPa
The installation site should have a flat ground, good ventilation, and no strong vibrations around the equipment
There is no strong electromagnetic field around the equipment, and there are no flammable, explosive, corrosive substances or dust around the equipment
Leave appropriate space for use and maintenance around the equipment